On December 16, 2021, the Federal Energy Regulatory Commission (“FERC”) issued Order No. 881 which finalized its proposed rulemaking from docket RM20-16-000. GDS Associates provided a summary of the proposed rulemaking in an earlier TransActions article and is providing this update with a summary of the final rule, including responsibilities for transmission providers and transmission owners. The final rule was published in the Federal Register on January 13, 2022, with an effective date of March 14, 2022. Transmission providers are required to submit their compliance filings by July 12, 2022, with an implementation deadline no later than July 12, 2025.
FERC established the following final definitions for ambient-adjusted and dynamic line ratings:
Ambient-Adjusted Rating (AAR): “a transmission line rating that: (1) applies to a time period of not greater than one hour; (2) reflects an up-to-date forecast of ambient air temperature across the time period to which the rating applies; (3) reflects the absence of solar heating during nighttime periods where the local sunrise/sunset times used to determine daytime and nighttime periods are updated at least monthly, if not more frequently; and (4) is
calculated at least each hour, if not more frequently.”
Dynamic Line Rating (DLR): “a transmission line rating that: (1) applies to a time period of not greater than one hour; and (2) reflects up-to-date forecasts of inputs such as (but not limited to) ambient air temperature, wind, solar heating intensity, transmission line tension, or transmission line sag.”
FERC ruled that transmission providers must use AARs for
If the equipment is affected by ambient air temperature, it requires an AAR. If it is not affected by ambient air temperature, an exception can be utilized consistent with good utility practice. AARs must incorporate a set of electrical equipment ratings that collectively operate as a single bulk electric system element (e.g., transformers, relay protective devices, terminal equipment, and series and shunt compensation devices) and that the most limiting component from that set determines the transmission line rating.
Ratings must be provided in a table or database format and cover the range of local historical temperatures +/- 10° Fahrenheit for the area where the equipment is located. Ratings must be provided in increments for every 5 degrees or less, but forecasting margin is allowed consistent with good utility practice.
FERC ruled that transmission providers must use seasonal line ratings for evaluating transmission service requests that will end beyond 10 days from the date of the request. Similar to AARs, transmission providers must also use seasonal line ratings (SLRs) when determining to curtail, interrupt, or redispatch transmission service beyond the next 10 days. SLRs must utilize at least 4 seasons that “reasonably reflect portions of the year where expected high temperatures are relatively consistent.” Seasonal ratings must be recalculated at least annually using historical temperatures.
Transmission providers must use uniquely determined emergency ratings for contingency analysis in the operations horizon and in post-contingency simulations of constraints. These must incorporate adjustments for ambient air temperature and solar heating impacts and include the amount of time the equipment can operate at the higher current.
Transmission owners are allowed to develop the methodology for emergency ratings, but they must be calculated separately from normal ratings. However, emergency ratings must still consider ambient air temperatures and impacts (or the lack thereof) from solar radiation.
FERC declined to mandate DLR implementation like AARs and SLRs but did open a new docket to “further explore” in AD22-5-000.
FERC will allow exceptions to the required AARs and SLRs if the transmission line rating is not affected by ambient air temperature or where a transmission provider an alternate rating is needed to ensure the safety and reliability of the transmission system. Exceptions must be reviewed every 5 years or less to determine whether it should endure.
FERC required RTOs/ISOs to establish and maintain the systems and procedures necessary to allow transmission owners in their regions to electronically update transmission line ratings on at least an hourly basis. TPs must also verify but not audit these ratings. Consistent with the NOPR, RTOs/ISOs must revise their dispatch and unit commitment models to implement AARs for both day ahead and real time markets and any intra-day reliability unit commitment or reliability assessment commitments.
Public utility transmission owners must share transmission
line ratings and methodologies with their transmission provider(s) and with market monitors in RTOs/ISOs. Transmission providers must share their transmission owners’ transmission line ratings and methodologies with any transmission provider(s) upon request. Transmission providers must maintain a database of their transmission owners’ transmission line ratings and methodologies on the transmission provider’s Open Access Same-Time Information System (OASIS) site or another password-protected website. Transmission providers must post on OASIS or another password-protected website any uses of exceptions or temporary alternate ratings.
GDS recommends the following steps to be ready for the line rating NOPR and its eventual implementation:
GET IN FRONT OF THE ISSUE: The Compliance Filings are due on July 12, 2022. Participate in various associations such as APPA (American Public Power Association) and NRECA (National Rural Electric Cooperative Association) to learn best practices from others. Read up on Order 881 so you are familiar with what you need to do.
START EVALUATING YOUR CONTRACTS: Begin reviewing your power supply and transmission contracts to understand how any changes to facility ratings impacts short-term deliverability, interconnection rights, transmission service reservations and tagging procedures, and curtailment/force majeure provisions.
START EVALUATING PROCESS CHANGES: Start doing your
research now to look at tools and equipment you will need to implement Order 881. Begin assessing your NERC Standards documentation and OATT (Open Access Transmission Tariffs) processes such as your Facility Rating Methodology, ATCID, CBMID, TRMID, TPL (Transmission Planning) practices and IROL/SOL methodology. Leverage the expertise of your consultants to assist in the transition.
START EVALUATING HARDWARE AND SOFTWARE CHANGES: Talk to your SCADA and OASIS vendors by communicating what you need. Make sure they see Order 881 the way you see it and ask questions when you do not agree.
KEEP AN EYE OUT FOR DISCUSSIONS REGARDING IMPLEMENTATION OF ANYTHING RELATED TO DYNAMIC LINE RATINGS: FERC is certainly not done with this issue. GDS will also be tracking this and will be ready to assist with any regulatory filings or technical assessments when the time comes.